Sign In | Join Free | My hardware-wholesale.com
hardware-wholesale.com
Products
Search by Category
Home > Circuit Breakers >

10KV Indoor Gas Insulated Air Load Break Switch With Fuse

Categories Air Load Break Switch
Brand Name: XG
Model Number: FZN21
Certification: ISO,CCC
Place of Origin: XIAN
MOQ: 1 SET
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 2000 SETS
Delivery Time: 3-7 DAYS
Packaging Details: WOODEN CASE
Function: Switch on and off normal load current
Installation Location: power plants, substations and power systems etc
Warranty: 12 months
OEM: Yes
Package: exporting standard package
MOQ: 1set
Operation type: electric or manual
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

10KV Indoor Gas Insulated Air Load Break Switch With Fuse

1.FZN21-12KV 11KV 10KV indoor Gas Insulated Air Load Break Switch


FZN21-12(R)D/T125-31.5 Series Indoor AC high voltage load switch- fuse combination units appliances for three-phase AC 10kV, 50Hz power system, or with the complete power distribution equipment and loop-network switch cabinet , combined substation and other ancillary uses, is widely used in urban network construction and transformation engineering, industrial and mining enterprises, high-rise buildings and public facilities ,can be used as ring power supply unit or terminal equipment, play power distribution, control and protection.

Technical performance of the products meet the IEC publication 60265-1/FDIS “high voltage switches, Part 1: Rated voltages below 1kV over 52kV high voltage load switch”, IEC60420 “High Voltage AC load switch – fuse combination units”; and CB16926 “AC High-voltage load switch - fuse combination units”, GB3804 “3-63kV AC high voltage switches” requirement.


2.Product parameter data


NoItemUnitValue
1Rated voltagekV12
2Rated frequencyHz50
3Rated currentA630125
4Rated insulation level1min power frequency withstand voltagekVArc-quenching chamber fracture 48
(effective value)Earth , phase 42, insulating fracture 48
Lightning impulse withstand voltage (peak)Earth , phase 75, insulating fracture 85
5Rated dynamic current (peak)kA50
64S thermal currentkA20
7Rated power load breaking currentA630
8Rated closed-loop breaking currentA630
9Rated cable charge breaking currentA10
10Rated breaking no-load transformer capacityKVA1250
11Rated breaking AC currentA3150
12Rated short-circuit closed currentkA50
13Rated current breaking timestimes2000
14Mechanical lifetimes10000
15Permitted wear-thickness of vacuum arc-quenching chamber contactmm2
16Manual operating torqueNm>200

3.Environmental application


A. The ambient air temperature: Max.: +40 °C. Min: -10 °C.

B. The altitude ≤ 1000m.

C. The relative humidity of air. daily average ≤ 90%. monthly average ≤ 95%.

D. The ambient air should not be obviously polluted by corrosively or the flammability gas and gleam. etc.

E. Without frequent shake.

F. Environment degree: grade Ⅱ.

4.Technical diagram


5.Warehouse view