Sign In | Join Free | My hardware-wholesale.com
hardware-wholesale.com
Products
Search by Category
Home > Transformers >

Indoor 10KV Low Voltage High Current Transformer Accuracy Class 0.5 Multiple Installation

Categories Instrument Current Transformer
Brand Name: GFUVE
Model Number: GFLZZ0973-10G2
Certification: CE, UL, KEMA, ISO9001
Place of Origin: BEIJING CHINA
MOQ: 3 PCS
Price: Negotiable
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 10000 PCS/MONTH
Delivery Time: 2-3 weeks
Packaging Details: Standard Export Carton Box
Name: Resin 10KV Accuracy Class 0.5 Instrument Current Transformer Indoor
Rated primary current: 5-1250A
Rated load: ≤15VA
Rated secondary current: 5A or 1A
Material: Epoxy resin
Weight: 25kg
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Indoor 10KV Low Voltage High Current Transformer Accuracy Class 0.5 Multiple Installation


Resin 10KV Accuracy Class 0.5 Instrument Current Transformer Indoor


Introduction


Instrument transformers are high accuracy class electrical devices used to isolate or transform voltage or current levels. The most common usage of instrument transformers is to operate instruments or metering from high voltage or high current circuits, safely isolating secondary control circuitry from the high voltages or currents. The primary winding of the transformer is connected to the high voltage or high current circuit, and the meter or relay is connected to the secondary circuit.
Instrument transformers may also be used as an isolation transformer so that secondary quantities may be used in phase shifting without affecting other primary connected devices.
Current transformers (CT) are a series connected type of instrument transformer. They are designed to present negligible load to the supply being measured and have an accurate current ratio and phase relationship to enable accurate secondary connected metering.
Current transformers are often constructed by passing a single primary turn (either an insulated cable or an uninsulated bus bar) through a well-insulated toroidal core wrapped with many turns of wire. This affords easy implementation on high voltage bushings of grid transformers and other devices by installing the secondary turn core inside high-voltage bushing insulators and using the pass-through conductor as a single turn primary.



PARAMETERS


Technical parameters 
StandardsIEC60044; IEC 61869; ANSI/IEEE C57.13
Rated primary current5-1250A
Rated load≤15VA
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Rated short-time thermal current140kA, 1S
Rated dynamic current350kA
Rated insulation level12/42/75KV
FS≤10
Mechanical parameters 
MaterialEpoxy resin
Weight (kg)25
Operating conditions 
Operating temperature-25°C to +55°C
Daily average temp<+40°C
Storage temperature-40°C to +70°C
Altitude<1000 meters
ConditionNo existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.



TECHNICAL DATA


Ratied Primary Current(A)Class CombinationAccuracy class and Rated output(VA)Short-time thermal current
(kA/S)
Rated dynamic current
(kA)
0.510P
5-1500.2(S)/10P
0.5/10P
1015150 I1n375 I1n
2003690
30045100
400-60063150
800-1000100250
1250140350


Overall Dimensions

Quality Indoor 10KV Low Voltage High Current Transformer Accuracy Class 0.5 Multiple Installation for sale
Send your message to this supplier
 
*From:
*To: Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0